//IDX_BUS Defines constants for named column indices to bus matrix. // Example: // // [PQ, PV, REF, NONE, BUS_I, BUS_TYPE, PD, QD, GS, BS, BUS_AREA, VM, ... // VA, BASE_KV, ZONE, VMAX, VMIN, LAM_P, LAM_Q, MU_VMAX, MU_VMIN] = idx_bus; // // Some examples of usage, after defining the constants using the line above, // are: // // Pd = bus(4, PD); % get the real power demand at bus 4 // bus(:, VMIN) = 0.95; % set the min voltage magnitude to 0.95 at all buses // // The index, name and meaning of each column of the bus matrix is given // below: // // columns 1-13 must be included in input matrix (in case file) // 1 BUS_I bus number (positive integer) // 2 BUS_TYPE bus type (1 = PQ, 2 = PV, 3 = ref, 4 = isolated) // 3 PD Pd, real power demand (MW) // 4 QD Qd, reactive power demand (MVAr) // 5 GS Gs, shunt conductance (MW demanded at V = 1.0 p.u.) // 6 BS Bs, shunt susceptance (MVAr injected at V = 1.0 p.u.) // 7 BUS_AREA area number, (positive integer) // 8 VM Vm, voltage magnitude (p.u.) // 9 VA Va, voltage angle (degrees) // 10 BASE_KV baseKV, base voltage (kV) // 11 ZONE zone, loss zone (positive integer) // 12 VMAX maxVm, maximum voltage magnitude (p.u.) // 13 VMIN minVm, minimum voltage magnitude (p.u.) // // columns 14-17 are added to matrix after OPF solution // they are typically not present in the input matrix // (assume OPF objective function has units, u) // 14 LAM_P Lagrange multiplier on real power mismatch (u/MW) // 15 LAM_Q Lagrange multiplier on reactive power mismatch (u/MVAr) // 16 MU_VMAX Kuhn-Tucker multiplier on upper voltage limit (u/p.u.) // 17 MU_VMIN Kuhn-Tucker multiplier on lower voltage limit (u/p.u.) // // additional constants, used to assign/compare values in the BUS_TYPE column // 1 PQ PQ bus // 2 PV PV bus // 3 REF reference bus // 4 NONE isolated bus // // See also DEFINE_CONSTANTS. // MATPOWER // Copyright (c) 1996-2016, Power Systems Engineering Research Center (PSERC) // by Ray Zimmerman, PSERC Cornell // // This file is part of MATPOWER. // Covered by the 3-clause BSD License (see LICENSE file for details). // See https://matpower.org for more info. // define bus types PQ = 1; PV = 2; REF = 3; NONE = 4; // define the indices BUS_I = 1; // bus number (1 to 29997) BUS_TYPE = 2; // bus type (1 - PQ bus, 2 - PV bus, 3 - reference bus, 4 - isolated bus) PD = 3; // Pd, real power demand (MW) QD = 4; // Qd, reactive power demand (MVAr) GS = 5; // Gs, shunt conductance (MW at V = 1.0 p.u.) BS = 6; // Bs, shunt susceptance (MVAr at V = 1.0 p.u.) BUS_AREA = 7; // area number, 1-100 VM = 8; // Vm, voltage magnitude (p.u.) VA = 9; // Va, voltage angle (degrees) BASE_KV = 10; // baseKV, base voltage (kV) ZONE = 11; // zone, loss zone (1-999) VMAX = 12; // maxVm, maximum voltage magnitude (p.u.) (not in PTI format) VMIN = 13; // minVm, minimum voltage magnitude (p.u.) (not in PTI format) // included in opf solution, not necessarily in input // assume objective function has units, u LAM_P = 14; // Lagrange multiplier on real power mismatch (u/MW) LAM_Q = 15; // Lagrange multiplier on reactive power mismatch (u/MVAr) MU_VMAX = 16; // Kuhn-Tucker multiplier on upper voltage limit (u/p.u.) MU_VMIN = 17; // Kuhn-Tucker multiplier on lower voltage limit (u/p.u.)